Automatic
Power Factor Controller Type 1179 The
Syntron Truly Intelligent Automatic Power Factor Controller type 1179
is specially designed to provide accurate and reliable control of
Power Factor of an electrical installation.
1179
has Microcontroller technology. This is a Syntron exclusive
trademarked as COSROBOTTM
. COSROBOTTM
. technology evolved at Syntron specifically for us ein APFCRs where
the problems of electrical noise, transients etc, Are accentuated,
and normal microprocessor technology fails under such condition.
1179
is a quantum leap over the other no-intelligent APFCRs like 1143.
Function When switched on first, the 1179 measures
itâs environment, and tells the user if there is anything wrong.
Thus if the load current is extremely low (below about 0.5%) it gives
a different display, if your connections are not correct, it gives an
alarm, etc.
Once it knows that the panel is correctly
connected in the system, it measures all capacitors under its control
by switching them one by one, and store their valves and location
(stage nos.) In memory. It them measures the Kvar at the main income
and calculates the âBEST FITâ� â i.e. The stages that when
switched on would provide the best possible power factor without
allowing it to go leading.
1179 then proceeds to switch them
on one by one, all the time assessing the effect on the system, and
re-calculating the Kvar requirement. The largest capacitor among
those destined to be on is switched on first, so that the Power
Factor is switched on first, so that the Power Factor is brought up
as quickly as possible.
It switches off the capacitors one by
one in like fashion, if the Power Factor goes leading, but this time
switching the smallest capacitor off first. Each stage of the
1179 has a corresponding software timer in memory. Thus whenever a
stage is switched off the times begins counting 60 seconds, 1179 then
does not switch it on even if needed, because that capacitor is
charged, and re-switching it would ruin it on transients. 1179 then
re-calulates and switches on other combination that will do the job.
However the capacitor is used immediately after the timing is
over.
Manual Control of the 1179 is also unique. You can
select any stage and switch ONLY that stage on or off, without
affecting the other stages.
Specifications Voltage : 400-440 V
(specify one) three phase three wire 50 Hz nominal 110V three
phase versions available on request. Current :
Through CT on the Main Incomer. 1 Amp or 5 Amp secondary. Low
Current Cutout : Factory set at 1%. Display reads 1. uuu
when the current is too low. Wrong Connections :
Three voltage wires and two wires from the CT on the main incomer
connect the APFCR in the electrical system. The wiring must be made
correctly. The APFCR switches off all stages and displays 2.uuu to
warn the operator. This condition persists till correct connections
are made. Meter: 4 digit Digital Meter:Range:0.000 lag â
1.000 â 0.000 lead. PF Setting Range : The
controller being intelligent, you have no setting to make. It
provides the best possible power factor under the system
constraints. Capacitor Swithing : Standard Models
are for 4,6,8 and 10 stages, The capacitors are switched in reverse
order of their size after calculating the requirements, i.e. the
largest one in the chosen group is switched on first. The capacitors
are switched off in the order of their size, i.e. the smallest
capacitor is switched off first. Contact Rating :
Each contact is rated for maxima of 230 V, 5 Amps AC resistive loads.
Provide a 2Amps fuse in the Common terminal, higher rating fuse will
cause damage to controller in case of a fault in the contractor
system. Dimension: Front Bezel : 144mm X
144mm. Panel Cutout: 138mm X 138mm. Depth Behind Panel:
100mm, including terminals. Weight: Approx 2 kg
- Field
proven design
- 4 Digit
Digital Power Factor Meter for accurate measurement.
- Built in
software timers for fast correction yet ensuring capacitor safety.
- Reliable
COSROBOTTM Technology.
- Available in
4, 6, 8, and 10 stage models.
- Special
Versions available for thyristor real time control.
- Built in
Syntron reliability.
- Special Alarm
control provided for wrong external connection, insufficient
capacitors etc.
- Unique built
in manual control to enable selection of the precise step to switch
on or off.
- Compact DIN
Std Flush Mounting 144 X 144X100mm Case.
- Sensitivity
better than 1% (50 Milli AMPs).
- No
settings to make.
- Self
learning. No site programming.
- Truly
intelligent Kvar based system for perfect control.
- Equalizes the
duty cycles on same value Capacitors.
- Measures Kvar
of each stage automatically.
- Built in
Syntron Reliability.
- Special versions available for
'fast discharge' capacitors
|